1408
Anchor for push-through mounting in M&E services and plant construction in concrete tensile zones. This anchor combines high permissible loads with close edge and centre distances.
Suitable for anchoring in cracked and non-cracked concrete – fixation of pipelines, channels, brackets, etc. in closed rooms – except for damp locations.
Supplied with washer and hexagon nut.
1. | Drill bore hole according to the minimum bore hole depth perpendicularly to the surface. |
2. | Remove dirt from hole. |
3. | Drive the anchor into concrete up to its embedment mark. |
4. | Immediately resilient after tightening with the torque wrench Tinst indicated in the table below. Advices of the mounting instruction are to be respected! |
Standard anchoring depth:
Anchor size | M8 | M10 | M12 | M16 |
---|---|---|---|---|
Perm. load 1) tension C20/25 2) [kN] | 2.4 | 4.3 | 7.6 | 11.9 |
C25/30 2) [kN] | 2.6 | 4.7 | 8.3 | 13.0 |
C30/37 2) [kN] | 2.9 | 5.2 | 9.3 | 14.5 |
C40/50 2) [kN] | 3.4 | 6.1 | 10.8 | 16.8 |
C50/60 2) [kN] | 3.7 | 6.6 | 11.8 | 18.5 |
Perm. load 1) oblique ≥ C20/25 2) [kN] | 7.0 | 11.5 | 17.1 | 31.4 |
Perm. bending moment 1) [Nm] | 13.1 | 26.9 | 46.9 | 123.4 |
Min. thickness of component hmin ≥ [mm] | 100 | 120 | 140 | 170 |
(3 hef ) Charact. centre distance scr [mm] | 138 | 180 | 210 | 255 |
(1,5 hef ) Charact. edge distance ccr [mm] | 69 | 90 | 105 | 127.5 |
Min. centre distance s at/edge distance c ≥ [mm] | 40/70 | 45/70 | 60/100 | 60/100 |
Min. edge distance c at/centre distance s ≥ [mm] | 40/80 | 45/90 | 60/140 | 60/180 |
Effective anchoring depth hef [mm] | 46 | 60 | 70 | 85 |
Nominal diameter of drill d0 [mm] | 8 | 10 | 12 | 16 |
Depth of bore hole h1 ≥ [mm] | 60 | 75 | 90 | 110 |
Anchoring torque Tinst [Nm] | 20 | 25 | 45 | 90 |
Perm. load 3) for fire exposure | ||||
Perm. load R30 perm. F [kN] | 1.25 | 2.25 | 4.0 | 6.25 |
Perm. load R60 perm. F [kN] | 1.1 | 1.9 | 3.0 | 5.6 |
Perm. load R90 perm. F [kN] | 0.8 | 1.4 | 2.4 | 4.4 |
Perm. load R120 perm. F [kN] | 0.7 | 1.2 | 2.2 | 4.0 |
1) Loads for single anchors without influence of edge distances
2) Cracked concrete (option 1)
3) Edge/Centre distances in case of fire – respective approval is to be respected
Reduced anchoring depth:
Anchor size | M8 | M10 | M12 | M16 |
---|---|---|---|---|
Perm. load 1) tension C20/25 2) [kN] | 2.4 | 3.6 | 6.1 | 9.0 |
C25/30 2) [kN] | 2.6 | 3.9 | 6.6 | 9.8 |
C30/37 2) [kN] | 2.9 | 4.3 | 7.4 | 10.9 |
C40/50 2) [kN] | 3.4 | 5.1 | 8.6 | 12.7 |
C50/60 2) [kN] | 3.7 | 5.5 | 9.4 | 13.9 |
Perm. load 1) oblique ≥ C20/25 2) [kN] | 7.0 | 10.4 | 14.5 | 21.6 |
Perm. bending moment 1) [Nm] | 13.1 | 26.9 | 46.9 | 123.4 |
Min. thickness of component hmin ≥ [mm] | 80 | 80 | 100 | 140 |
(3 hef ) Charact. centre distance scr [mm] | 105 | 120 | 150 | 195 |
(1,5 hef ) Charact. edge distance ccr [mm] | 52.5 | 60 | 75 | 97.5 |
Effective anchoring depth hef [mm] | 35 | 40 | 50 | 65 |
Nominal diameter of drill d0 [mm] | 8 | 10 | 12 | 16 |
Depth of bore hole h1 ≥ [mm] | 49 | 55 | 70 | 90 |
Anchoring torque Tinst [Nm] | 20 | 25 | 45 | 90 |
Perm. load 3) for fire exposure | ||||
Perm. load R30 perm. F [kN] | 1.25 | 1.82 | 3.18 | 4.72 |
Perm. load R60 perm. F [kN] | 1.1 | 1.82 | 3.0 | 4.72 |
Perm. load R90 perm. F [kN] | 0.8 | 1.3 | 1.9 | 3.5 |
Perm. load R120 perm. F [kN] | 0.6 | 1.0 | 1.3 | 2.5 |
1) Loads for single anchors without influence of edge distances
2) Cracked concrete (option 1)
The safety factor accord. to ETAG is respected. Values of the mentioned approval are valid and could be seen in the latest issue under www.sikla.com/service/downloads.
Material: | Steel, galvanised |
Sikla Approval ETA-10/0259
FM-Approval for M10, M12, M16 only for Standard anchoring depth
VdS compliant for all sizes
Shock approval issued by the Federal Office for Civil Defence, Bern (Switzerland)
The types marked * are not part of the Seismic-Approval.
tfix = max. effective length [mm]
Bolt Anchor AN BZ plus – ETA 10/0259PDF | 15.2 MB
FM – Sikla Anchors ANPDF | 187.3 KB
The types marked with * are not part of the Seismic approval.
1) Delivery date on request – goods are procured to order.
tfix = max. usable length [mm]